Control Valve Sizing — Liquid (Cv / Kv)
Finds the flow coefficient a control valve needs to pass a liquid flow at a given pressure drop, as Cv (US units) and Kv (metric), using the IEC 60534-2-1 / ISA-75.01.01 sizing equations for turbulent, non-viscous liquids [1]. It also checks for choked flow, where cavitation or flashing caps the flow. Instrument engineers use it to pick a valve from a maker’s Cv tables.
Equations
FF = 0.96 − 0.28·√(Pv/Pc)
ΔPchoked = FL2·(P1 − FF·Pv)
Cv = Q·√(SG/ΔPs) Kv = 0.865·Cv
Q is the flow, P1 the absolute upstream pressure and ΔP the drop across the valve. SG is the liquid’s density at flowing temperature divided by that of water at 15 °C. Pv is its vapor pressure and Pc its critical pressure, both absolute. FF is the liquid critical pressure ratio factor. FL is the liquid pressure recovery factor of the valve. ΔPs is the sizing drop: ΔP, or ΔPchoked if that is smaller. In the Cv equation Q is in US gpm and ΔPs in psi. Kv is in m³/h at a drop of 1 bar.
Inputs
- Choosing a Liquid fills in SG, Pv and Pc for water from 5 to 100 °C [3], [4], or for ethanol or methanol at 25 °C [5], [6].
- Choosing a Valve Style fills in the typical FL at full travel from IEC 60534-2-1 Table 2 [1]. Use the maker’s FL when you know it [2]. A rotary valve’s FL falls as it opens.
Limits and common mistakes
- The valve is taken as line-size, with no reducers (FP = 1). Reducers lower the effective capacity.
- Viscous liquids need the correction FR, which is not applied.
- Use absolute pressures for P1 and Pv. A gauge P1 understates ΔPchoked.
- “Choked” means more drop gives no more flow, and the valve will cavitate or flash. Cavitation damage can start below ΔPchoked.
- Pick a valve that passes the design flow at about 60 to 80 % of travel.
Worked example
A valve must pass 60 m³/h of water at 90 °C, with 400 kPa absolute upstream and 250 kPa available for the drop. Will a 70°-open butterfly valve work, or is a globe valve needed?
- Enter Flow Rate 60 m³/h, Upstream Pressure 400 kPa and Pressure Drop Across Valve 250 kPa.
- Choose Liquid Water, 90°C. It fills in SG = 0.966, Pv = 70.182 kPa and Pc = 22,064 kPa.
- Choose Valve Style Butterfly, swing-through disc, 70° open (FL 0.62) and press Solve:
Liquid critical pressure ratio factor FF: 0.944208
Choked pressure drop ΔP_choked: 128.287 kPa
Flow condition: Choked (flashing/cavitating) — sized at ΔP_choked
Required Cv (US units): 60.1979
Required Kv (metric): 52.0712 - The butterfly valve would cavitate. Choose Valve Style Globe, single port, contoured plug, flow tends to open (FL 0.90) and press Solve:
Liquid critical pressure ratio factor FF: 0.944208
Choked pressure drop ΔP_choked: 270.324 kPa
Flow condition: Non-choked
Required Cv (US units): 43.1224
Required Kv (metric): 37.3009
Check by hand with the SI form of the equation, Kv = 10Q·√(SG/ΔP) with ΔP in kPa: FF = 0.96 − 0.28 × √(70.18/22,064) = 0.9442, and ΔPchoked = 0.81 × (400 − 66.27) = 270.3 kPa, more than 250 kPa. Then Kv = 600 × √(0.9662/250) = 37.30, and Cv = 37.30/0.865 = 43.1.