Minimum Uniformly Distributed Live Loads

Occupancy / UseLo (psf)Lo (kN/m²)
Residential (one- and two-family) — all areas except stairs401.92
Residential — habitable attics and sleeping areas301.44
Residential — uninhabitable attic, no storage100.48
Residential — uninhabitable attic, with storage200.96
Residential (other) — private rooms and their corridors401.92
Residential (other) — public rooms and their corridors1004.79
Offices502.40
Office lobbies & first-floor corridors1004.79
Office corridors above first floor803.83
Access floors — computer use1004.79
Assembly areas — fixed seats602.87
Assembly areas — movable seats, lobbies, platforms1004.79
Dining rooms and restaurants1004.79
Gymnasiums, dance halls and ballrooms1004.79
Hospitals — operating rooms, laboratories602.87
Hospitals — patient rooms401.92
Schools — classrooms401.92
Schools — corridors above first floor803.83
Retail — first floor1004.79
Retail — upper floors753.59
Light manufacturing1256.00
Heavy manufacturing25011.97
Storage warehouses — light1256.00
Storage warehouses — heavy25011.97
Libraries — reading rooms602.87
Libraries — stack rooms1507.18
Garages — passenger vehicles401.92
Stairs and exit ways1004.79
Roofs, ordinary flat, pitched and curved200.96

Unreduced uniform live loads Lo from ASCE/SEI 7-22 Table 4.3-1 [1], the edition the 2024 IBC [2] adopts (these rows are unchanged from 7-16, which the 2021 IBC adopts). The full table also gives concentrated loads, whether live load reduction is permitted, and many more occupancies; check the edition your jurisdiction uses.

Typical Dead Load Estimates

Material / AssemblyApprox. Weight
Normal-weight reinforced concrete150 pcf
Lightweight concrete90–115 pcf
Structural steel490 pcf
Concrete slab, per inch of thickness~12.5 psf/in
Wood floor/roof framing + sheathing7–10 psf
Asphalt shingle roofing2–3 psf
Built-up roofing (BUR)5–6 psf
Metal roof deck, uninsulated2–3 psf
Suspended acoustic ceiling1–2 psf
Mechanical/electrical allowance2–5 psf
Gypsum board, per 5/8 in layer~2.2 psf
Brick veneer, 4 in~40 psf
CMU wall, 8 in hollow~55 psf
CMU wall, 8 in grouted solid~85 psf

Early-design estimates only — confirm against manufacturer data or ASCE 7 Commentary for a specific assembly.

Basic Load Combinations

No.Strength Design (LRFD), §2.3.1 and §2.3.6No.Allowable Stress Design (ASD), §2.4.1 and §2.4.5
1a1.4D1aD
2a1.2D + 1.6L + (0.5Lr or 0.3S or 0.5R)2aD + L
3a1.2D + (1.6Lr or 1.0S or 1.6R) + (L or 0.5W)3aD + (Lr or 0.7S or R)
4a1.2D + 1.0(W or WT) + L + (0.5Lr or 0.3S or 0.5R)4aD + 0.75L + 0.75(Lr or 0.7S or R)
5a0.9D + 1.0(W or WT)5aD + 0.6(W or WT)
61.2D + Ev + Eh + L + 0.15S6aD + 0.75L + 0.75[0.6(W or WT)] + 0.75(Lr or 0.7S or R)
70.9D − Ev + Eh7a0.6D + 0.6(W or WT)
  81.0D + 0.7Ev + 0.7Eh
  91.0D + 0.525Ev + 0.525Eh + 0.75L + 0.1S
  100.6D − 0.7Ev + 0.7Eh

ASCE/SEI 7-22 basic combinations [1]. D = dead, L = live, Lr = roof live, S = snow, R = rain, W = wind, WT = tornado, Eh = horizontal seismic load effect ρQE, Ev = vertical seismic load effect (0.2SDSD). 7-22 ground snow loads are strength-level, hence the snow factors of 1.0, 0.3 and 0.15 (LRFD) and 0.7 and 0.1 (ASD). The factor on L in LRFD 3a, 4a and 6 may be 0.5 where Lo ≤ 100 psf (4.78 kN/m²), except in garages and places of public assembly. Where S is a companion load (LRFD 2a, 4a and 6; ASD 4a, 6a and 9) it may be the flat or the sloped roof snow load. With WT, the roof term of LRFD 4a may be 0.5(Lr or R) and that of ASD 6a 0.75(Lr or R). Flood, ice, self-straining and overstrength (Emh) combinations, and the rules for fluid and earth-pressure loads, are in §2.3 and §2.4.

Wind Exposure Categories

CategorySurface RoughnessApplies Where
BUrban and suburban areas, wooded areas, or other terrain with many closely spaced obstructions the size of single-family homes or largerRoughness B extends upwind more than 1,500 ft (457 m) for a mean roof height up to 30 ft (9.1 m); for taller buildings, more than 2,600 ft (792 m) or 20 times the height, whichever is greater
COpen terrain with scattered obstructions generally under 30 ft (9.1 m) tall, including flat open country and grasslandsEvery case where B or D does not apply
DFlat, unobstructed areas and water surfaces, including smooth mud flats, salt flats and unbroken iceRoughness D extends upwind more than 5,000 ft (1,524 m) or 20 times the height, whichever is greater; also where the roughness just upwind is B or C but the site is within 600 ft (183 m) or 20 times the height of such a D condition

ASCE/SEI 7-22 §26.7.2 and §26.7.3 [1]. The exposure is set for each wind direction from the two 45° upwind sectors; in a transition zone, use the category giving the larger wind forces.