Transformer Overcurrent Protection, 1000 V and Less

Table 450.3(B) percentages from NEC 2017 [1]; standard ratings from Table 240.6(A), NEC 2023 [2]; nominal voltages from ANSI C84.1 [3]. For winding currents and core size of a small transformer, see the Transformer Sizing calculator.

Maximum Overcurrent Protection — Table 450.3(B)

Protection methodPrimary protection, rated primary currentSecondary protection (Note 2), rated secondary current
9 A or moreLess than 9 ALess than 2 A9 A or moreLess than 9 A

Maximum rating or setting as a percentage of the transformer’s rated current, transformers of 1000 V and less, NEC 2017 [1].

Notes to Table 450.3(B), in Short

NoteApplies toRule (paraphrased)
1The 125 % entriesWhere 125 % of rated current is not a standard fuse or nonadjustable breaker rating, the next higher standard rating is permitted. Other entries may not be exceeded.
2Secondary protectionUp to six breakers or six sets of fuses grouped in one location; their ratings added together may not exceed what one device would be allowed.
3Primary 250 % entriesWith the manufacturer’s coordinated thermal overload protection, arranged to interrupt the primary current, the primary device may be up to 6 × rated current (impedance up to 6 %) or 4 × (impedance over 6 % to 10 %).

Paraphrased from NEC 2017 [1]; read the code text before applying.

Standard Ampere Ratings — Table 240.6(A)

Fuses and inverse-time circuit breakers (A)

NEC 2023 [2], which added the 10 A rating; the picker’s standard ratings come from this list.