From the adjustment-factor pages of each NDS Supplement table. Multiply the reference value by every factor that applies.
Size factor CF, Tables 4A and 4F, by nominal width
Grades
Width
Fb, thickness
Ft
Fc
2″ & 3″
4″
Size factor CF, Tables 4B, 4D and 4E (d = actual depth, in)
Table
Applies to
Property
CF
CF = (12/d)1/9, calculated
d (in)
d (mm)
CF
Wet service factor CM, moisture content over 19 % for an extended time
Table
Fb
Ft
Fv
Fc⊥
Fc
E, Emin
Exceptions
Flat use factor Cfu on Fb, dimension lumber loaded on the wide face
Width
Tables 4A, 4B, 4F, thickness
Table 4C, 2″ thick
2″ & 3″
4″
Flat use factor Cfu, Table 4D Beams and Stringers loaded on the wide face (decking, Table 4E, is already flatwise)
Grade
Fb
E, Emin
Other properties
Repetitive member factor Cr on Fb
Table
Cr
Applies to
Spruce Pine (SPIB rules): factors on the Mixed Southern Pine values of Tables 4B and 4D, then E rounded to the nearest 100,000 psi, Emin to the nearest 10,000 psi, Fv and Fc⊥ down to a multiple of 5 psi, Fb, Ft and Fc down to a multiple of 50 psi (25 psi below 1,000 psi)
Fb
Ft
Fv
Fc⊥
Fc
E, Emin
Load Duration Factor CD
NDS Table 2.3.2. Applies to Fb and Fv, not to E or Emin; use the CD of the shortest-duration load in the combination.