Motor Branch-Circuit Protection

Maximum short-circuit and ground-fault protective device rating from the table full-load current [1] and the Table 430.52 percentages, which are from the 2017 edition [2]; full-load currents and standard ratings are from the 2023 edition [1]. See also the Motor Starting Current and Circuit Breaker/Fuse Sizing calculators.

Synchronous and dc motors are not in the picker (this site has no full-load currents for them), nor are motors over 1000 V, which Article 430 Part XI covers.

Full-Load Current, Single-Phase Motors — Table 430.248

hp115 V200 V208 V230 V

Amperes, NEC 2023 [1]. Use these table values, not the nameplate current, to size conductors and protection (430.6(A)(1)).

Full-Load Current, Three-Phase Motors — Table 430.250

hp115 V200 V208 V230 V460 V575 V2300 V

Amperes, induction motors (squirrel cage and wound rotor), NEC 2023 [1]; “—” = no table entry. The table’s synchronous-motor columns are not included.

Locked-Rotor Code Letters — Table 430.7(B)

Code letterLocked-rotor kVA per hp

Maximum Motor Branch-Circuit Protection — Table 430.52

Type of motorPercent of full-load current
Nontime-delay fuse1Dual-element (time-delay) fuse1Instantaneous-trip breakerInverse-time breaker2

NEC 2017 [2]. 1 Also used for time-delay Class CC fuses. 2 Also covers nonadjustable inverse-time breakers, which may be modified under 430.52(C)(1) Exc. No. 1 and 2. 3 200 % at most for low-torque, low-speed synchronous motors (usually 450 rpm or less) that start unloaded. Exceptions: 430.54.

Standard Ampere Ratings — Table 240.6(A)

Fuses and inverse-time circuit breakers (A)

NEC 2023 [1], which added the 10 A rating.