Pump Power & Affinity Laws
Finds the shaft power of a centrifugal pump at its duty point, then uses the affinity laws to predict its flow, head and power after a change of speed or an impeller trim. Engineers and technicians use it to size a variable-speed drive, to estimate the energy saved by slowing a pump, or to decide how much to trim an impeller. For fans, use the Fan Power & Affinity Laws calculator.
Equations
Ph = ρ·g·Q·H P = Ph/η
Ph is the hydraulic power given to the liquid, ρ its density, g the acceleration of gravity, Q the flow and H the pump’s total head. P is the shaft (brake) power and η the pump efficiency [1], [2]. In US units this is BHP = GPM × ft × SG/(3960 × η), with SG the specific gravity. You can enter the shaft power instead, from a pump curve or a motor reading. Picking a water temperature fills in ρ [4].
For a change of speed N or impeller diameter D, the affinity laws [2], [3] give
Q2/Q1 = (N2/N1)·(D2/D1)
H2/H1 = [(N2/N1)·(D2/D1)]2
P2/P1 = [(N2/N1)·(D2/D1)]3
Subscript 1 is the known point and 2 the new one. The efficiency is taken as unchanged. The Live Pump Curve panel draws an assumed curve through your one point (shutoff head 1.25×H1) and the same curve scaled by the affinity laws. Only the scaling is exact; the shape is illustrative.
Limits and common mistakes
- The laws move the duty point along a parabola through zero flow and zero head. A system with static head (a lift, or a pressure to hold) does not follow it, so a speed cut lowers the flow more than the laws predict. Find the new point where the scaled pump curve crosses the system curve.
- The diameter law is only approximate. Trim no more than about 10 to 20 % of the impeller, and expect some loss of efficiency [3].
- Check the new point’s NPSH required and the motor size before speeding a pump up.
Worked example
A chilled-water pump delivers 300 GPM at 80 ft of head, at 1,750 rpm with a 75 % efficient 10 in. impeller. A drive will run it at 1,450 rpm. What flow, head and power result?
- Enter Original Flow 300 GPM and Original Head 80 ft.
- Choose Original Power Calculate from flow, head, fluid and efficiency, then Fluid Water, 10°C, and enter Pump Efficiency 75.
- Enter Original Speed 1750 rpm and New Speed 1450 rpm.
- Enter Original Impeller Diameter and New / Trimmed Impeller Diameter both 10 in, and press Solve. The Solution shows:
Original Shaft Power (P1 = Ph/η): 6.03278 kW
Speed ratio N2/N1: 0.828571
New power P2: 3.43168 kW
New flow Q2 (US): 248.571 GPM
New head H2 (US): 54.9224 ft
Original power P1 (US): 8.09009 hp
New power P2 (US): 4.60196 hp
Check with the US formula: 300 × 80 × 1.0007/(3960 × 0.75) = 8.09 hp. The speed ratio cubed is 0.8286³ = 0.569, so a 17 % cut in speed saves 43 % of the shaft power, if the system has no static head.