Conductor Lookup

Values from NEC 2017 (NFPA 70-2017) Chapter 9 Tables 8 and 9, exactly as printed [1]; the site’s calculators each cite the NEC edition their own data came from. Use them in the Wire/Cable Sizing & Voltage Drop calculator, and the overall diameters in the Conduit Fill calculator.

DC Properties — NEC Chapter 9 Table 8

SizeStrandsAreaStrand diameterOverall diameterOverall areaCopper, uncoatedCopper, coatedAluminum
mm²cmilmmin.mmin.mm²in²Ω/kmΩ/kftΩ/kmΩ/kftΩ/kmΩ/kft

DC resistance at 75 °C (167 °F); Class B stranding, with the overall diameter of the circle around the strands. The kcmil sizes leave the cmil column blank because the size is the area. For 1500–2000 kcmil the printed coated-copper Ω/km values repeat the uncoated ones, while the Ω/kft values are about 3 % higher as for the other sizes.

AC Resistance & Reactance — NEC Chapter 9 Table 9

600 V cables, 3-phase, 60 Hz, 75 °C, three single conductors in conduit; ohms to neutral, Ω/1000 ft
SizeXL, all wiresAC resistance, uncoated copperAC resistance, aluminumEffective Z at 0.85 PF, uncoated copperEffective Z at 0.85 PF, aluminum
PVC, Al conduitSteel conduitPVCAlSteelPVCAlSteelPVCAlSteelPVCAlSteel

Conduit columns: PVC, aluminum (Al) or steel conduit. Effective Z = R × PF + XL × sin(arccos PF), tabulated at PF = 0.85; current × Z approximates the line-to-neutral voltage drop. No aluminum values at 14 AWG.